Common ampacity reference with a simplified derating calculator for conductor count and ambient temperature.
Multiple conductors in the same raceway require derating to account for heat buildup. Temperature also reduces safe ampacity.
A wire ampacity chart is used to answer a basic but important question: how much current can a conductor carry under the conditions of the installation. That answer depends on conductor material, insulation rating, terminal temperature limits, conductor count, and ambient temperature. NEC Table 310.16 is the reference many electricians start with before applying any corrections.
The table gives base ampacity values for copper and aluminum conductors under standard conditions. Actual allowed ampacity may still be reduced by terminal limits, small-conductor rules, conductor count, or ambient temperature.
Derating applies when multiple current-carrying conductors share the same raceway or cable and when ambient temperature exceeds the base condition used by the code table. Both adjustments may apply to the same circuit.
When the number of current-carrying conductors increases, the allowable ampacity is reduced by the applicable adjustment factor. This check is separate from conduit fill.
Ambient heat reduces usable ampacity. Attics, rooftops, and sun-exposed raceways may require a temperature correction factor before final conductor sizing is confirmed.
Conductors may be listed with 60C, 75C, or 90C insulation ratings, but usable ampacity is limited by the lowest-temperature termination in the circuit.
A conductor installed in a hot attic with several other current-carrying conductors may require both conductor-count adjustment and temperature correction before breaker size is finalized.
| AWG / kcmil | Copper Reference Values | Aluminum Reference Values | Common Application | ||||
|---|---|---|---|---|---|---|---|
| 60°C | 75°C | 90°C | 60°C | 75°C | 90°C | ||
| 14 | 20 | 20 | 25 | 15 | 15 | 20 | Lighting circuits |
| 12 | 20 | 25 | 30 | 15 | 20 | 25 | General purpose (20A) |
| 10 | 30 | 35 | 40 | 25 | 30 | 35 | Heavy loads (30A) |
| 8 | 40 | 50 | 55 | 35 | 40 | 45 | Large circuits (50A) |
| 6 | 55 | 65 | 75 | 40 | 50 | 55 | Subpanel feeders |
| 4 | 70 | 85 | 95 | 55 | 65 | 75 | Large feeders (100A) |
| 2 | 95 | 115 | 130 | 75 | 90 | 100 | Service entrance (125A) |
| 1 | 110 | 130 | 150 | 85 | 100 | 115 | Service entrance (150A) |
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 | Service entrance (150-175A) |
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 | Service entrance (200A) |
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 | Service entrance (225A) |
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 | Service entrance (250A) |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 | Large feeders (300A) |
| 300 kcmil | 240 | 285 | 320 | 190 | 230 | 255 | Utility feeders (300A+) |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 | Utility feeders (350A+) |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 | Utility feeders (400A+) |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 | Utility feeders (500A) |
| Number of Current-Carrying Conductors | Adjustment Factor | Practical Example |
|---|---|---|
| 1-3 | 100% (no derating) | Standard residential circuits; 3 wires in conduit |
| 4-6 | 80% | 4-6 circuits sharing a large conduit |
| 7-9 | 70% | Large industrial panel feeder with multiple circuits |
| 10-20 | 50% | Large cable tray with many feeder circuits |
| 21-30 | 45% | Massive feeder system with 25+ circuits |
| 31-40 | 40% | Utility distribution or data center feeder |
| 41+ | 35% | Extreme bundling; rarely seen in practice |